(110 VDC / 220 VDC) RCT2000 Series Intelligent Rectifier System

Dedicated Switching Power Supply for Power Systems | Ultra-Wide AC Input (90–290 Vac) | Modular & Hot-Pluggable | Intelligent Battery Management | Suitable for DC Power Panels in Substations and Power Plants

  1. 🔌 Ultra-wide AC Input: 90–290 Vac
  2. 🧩 Modular Hot-swappable Design
  3. 🔋 Intelligent Battery Management (Temperature Compensation, Equalization & Float Charging)
  4. 📊 Real-time Monitoring + Audible & Visual Alarms
  5. 🌐 RS485/SNMP Communication
Parameter110Vdc System220Vdc System
DC Output Voltage110Vdc (90~150V adjustable)220Vdc (198~286V adjustable)
Single Module Output Current20A10A
Maximum System Cabinet Capacity140A70A
Efficiency91.50%93%
Operating Temperature-40℃ ~ +55℃-40℃ ~ +55℃
Intelligent Rectifier System
FeatureDescription
Dedicated Power System DesignDesigned for 110V/220V DC panels in substations and power plants, providing stable DC power for relay protection, circuit breaker operations, and more
Ultra-Wide AC Input RangeInput voltage of 90–290Vac, suitable for harsh environments with large power grid fluctuations; derating design ensures operation even at low voltages
Modular Hot-Swap DesignRectifier modules support hot-swapping, allowing replacement or expansion without system shutdown, easy maintenance, and high system availability
Intelligent Battery ManagementFeatures automatic equalize/float charge switching, battery temperature compensation, low-voltage battery disconnect (LVBD), etc., extending battery life
Real-Time Status MonitoringLCD display shows real-time information such as battery voltage, total current, load current, fault alarms, etc.; audible and visual alarms provide alerts
Comprehensive ProtectionIncludes input over/under voltage protection, output overvoltage protection, overcurrent protection, short circuit protection, overtemperature protection, etc.
Wide Operating TemperatureOperates in a wide temperature range of -40℃ ~ +55℃, suitable for outdoor substations, border regions, and other extreme environments
Communication InterfaceStandard RS485, with optional SNMP card for integration into power system monitoring platforms
InputSingle
Input Voltage Range90Vac to 265Vac
Rate input Voltage110Vac / 220Vac
Normal Input100Vac to 240Vac
Frequency Range45Hz-65Hz
Max Input Current14.2A±10%@176Vac/2500W
Surge CurrentCompliant standard:ETSI300132-3
Efficiency≥93%@220Vac 100% Load
PF≥0.98@220Vac100% Load
Rate Capacity2500W(176Vac~265Vac)
1200W(90Vac~175Vac)
Input fuseL Wire ,Fuse 30A
Output Feature
Output Voltage+110Vdc
Output Voltage Regulation110±0.5Vdc
Output Range adjustable Range+90Vdc~+150Vdc
Line regulation±0.1%
Load regulation±0.5%
Voltage precision±0.5%
Current precision±0.5%
ripple coefficient≤0.5%
Output current deviation≤±0.3A
Current Sharing(176Vac~264Vac,50%~100% load)≤±5%
Min- Current0A
Rate current20A
Peaking current22A
Tempe. coefficient(1/℃)≤±0.02%
Rate Capacity2500W(176Vac~264Vac)
1200W(90Vac~175Vac)
BR483000
Input Feature
InputSingle
Input Voltage Range90Vac to 265Vac
Rate input Voltage110Vac / 220Vac
Normal Input100Vac to 240Vac
Frequency Range45Hz-65Hz
Max Input Current14.2A±10%@176Vac/2500W
Surge CurrentCompliant standard:ETSI300132-3
Efficiency≥93%@220Vac 100% Load
PF≥0.98@220Vac100% Load
Rate Capacity2500W(176Vac~265Vac)
1200W(90Vac~175Vac)
Input fuseL Wire ,Fuse 30A
Output Feature
Output Voltage+234Vdc
Output Voltage Regulation220±1Vdc
Output Range adjustable Range+198Vdc~+286Vdc
Line regulation±0.1%
Load regulation±0.5%
Voltage precision±0.5%
Current precision±0.5%
Output current deviation≤0.5%
Output current Regulate deviation≤±0.3A
Current Sharing(176Vac~264Vac,50%~100% load)≤±5%
Min- Current0A
Rate current10A
Peaking current11A
Tempe. coefficient(1/℃)≤±0.02%
Rate Capacity2500W(176Vac~264Vac)
1200W(90Vac~175Vac)
Substation⚡Provides charging modules for the 110V/220V DC panel in the station, ensuring reliable power for relay protection and circuit breaker operations
Power Plant🏭Provides DC charging for the power plant's operating power system; modular design supports hot-swapping for easy maintenance
Railway Traction Substation🚄Suitable for DC power systems in substations along railway lines
Industrial and Mining Enterprise Distribution Room🏗️Provides DC operating power for the high-voltage distribution room of the enterprise
What are the typical applications for the RCT2000 110V/220V series?

It is primarily designed for scenarios requiring high-voltage DC power supplies, such as power system substations, power plants, and railway traction substations.

It is recommended to use modules of identical specifications within the same system; modules with different voltage ratings cannot be mixed.

The unit comes standard with an RS485 interface and offers an optional SNMP card for integration with power system monitoring platforms.

It features functions such as automatic switching between equalization charging and float charging, battery temperature compensation, low-voltage battery disconnection, and battery testing.

Yes. The cabinet dimensions, power distribution configuration, and protection rating (IP rating) can all be customized to meet specific project requirements.

-40°C to +55°C; an optional heater is available to accommodate even lower-temperature environments.