CON1000 Series DC-DC Converters (24V/48V/110V/220V)

Fully Isolated Input and Output | Masterless Automatic Current Sharing Technology | Supports Parallel Operation of Up to 8 Units | Comprehensive Protection | Suitable for Conversion Between Various DC Voltage Levels

  1. 🔌 Fully Isolated Input and Output
  2. 🔗 Masterless Automatic Current Sharing; Supports Parallel Operation of up to 8 Units
  3. 🛡️ Comprehensive Protection (Over-voltage / Under-voltage / Short-circuit / Over-temperature)
  4. 📊 Efficiency ≥85%
  5. 🌡️ Temperature-Controlled Air Cooling
  • Input Voltage: 24V / 48V / 110V / 220Vdc
  • Output Voltage: 24V / 48V / 110V / 220Vdc (Various Combinations)
  • Output Current: 30A / 40A / 50A (Depending on Model)
  • Efficiency: ≥85%
  • Current Sharing Imbalance: ≤±5%
  • MTBF: 100,000 Hours
CON1000 Series DC-DC Converters (2)
CON1000 Series DC-DC Converters (4)
CON1000 Series DC-DC Converters (1)
CON1000 Series DC-DC Converters (3)
FeatureDescription
Fully Isolated Input and OutputAdopts isolation design with electrical isolation between input and output, ensuring safety and reliability, suitable for connections between systems with different voltage levels
Masterless Automatic Current Sharing TechnologyNo need to set master or slave modules when paralleling multiple units; automatically achieves current sharing, facilitating capacity expansion and improving system reliability
Comprehensive Protection FunctionsFeatures output overvoltage protection, output undervoltage protection, short circuit protection, and overtemperature protection, ensuring equipment and load safety
Wide Voltage Input RangeAdapts to fluctuations in different DC bus voltages; input undervoltage/overvoltage thresholds are configurable
High-Reliability DesignReliable circuit topology and advanced current control mode; MTBF reaches 100,000 hours
Temperature-Controlled Fan CoolingAutomatically adjusts fan speed based on temperature, reducing noise and extending fan life
Multiple Input-Output CombinationsSupports conversion between various voltage levels such as 24V, 48V, 110V, and 220V, flexibly adapting to different system requirements
19-Inch Rack MountStandard 2U height design, can be installed in standard cabinets, saving space
Model Selection Table
Input VoltageOutput Voltage30A40A50A
24Vdc (20-30V)24V
48V
110V
220V
48Vdc (40-50V)24V
48V
110V
220V
110Vdc (90-140V)24V
48V
110V
220V
220Vdc (180-270V)24V
48V
110V
220V
*Note: The specific model naming convention is Input Voltage-Output Voltage-Current, for example, a model with 48V input, 24V output, and 40A.*
Input Characteristics
ParameterSpecification
Input Undervoltage Point24V @ 20VDC; 48V @ 40VDC; 110V @ 90VDC; 220V @ 180VDC
Input Overvoltage Point24V @ 32VDC; 48V @ 60VDC; 110V @ 132VDC; 220V @ 270VDC
Output Characteristics
ParameterSpecification
Equalize Charge Voltage (Note: for battery charging applications)24V @ 26.4V (22.5-27.6V); 48V @ 52.8V (43-56.7V)
Float Charge Voltage24V @ 28.2V (24-29.8V); 48V @ 56.4V (48-57.6V)
Output Voltage Protection Point24V @ 1±1VDC; 48V @ 2±1VDC; 110V @ 135±1VDC; 220V @ 45±1VDC
Load Regulation≤0.2%
Line Regulation≤0.1%
Current Sharing Imbalance≤±5%
Noise Parameters
ParameterSpecification
Telephone Weighted Noise Voltage≤2mV (CCITT)
Peak-to-Peak Noise≤150mV
Broadband Noise≤50mV
Discrete Noise≤20mV
General Parameters
ParameterSpecification
Efficiency≥85%
Dynamic Response20% to 100% step load, recovery time ≤100μs
Parallel FunctionSupported, up to 8 units
Operating Temperature-10℃ ~ +50℃
Cooling MethodTemperature-controlled fan cooling
Mean Time Between Failures (MTBF)100,000 hours
Weight8kg
Dimensions482 * 240 * 88mm (2U)
Communication Base Station📡Converts the 48V battery bank voltage in the base station to 24V to power legacy communication equipment
Power SystemIn substations, converts the 220V DC panel voltage to 110V or 48V to supply loads with different voltage levels
Rail Transit🚄Converts the high-voltage DC from the train bus to various DC voltages required by onboard equipment
Industrial Control🏭Provides stable DC power for PLCs, sensors, instruments, etc.; input-output isolation ensures safety
Photovoltaic Energy Storage☀️Enables matching or voltage regulation between battery banks of different voltage levels in energy storage systems
What voltage conversions can the CON1000 series perform?

It supports bidirectional conversion among various voltage levels, including 24V, 48V, 110V, and 220V. Please refer to the model selection chart for specific details.

The isolated design prevents fault-induced voltage crosstalk and enhances system safety; it also facilitates connections between systems with differing grounding requirements.

It supports parallel operation of up to 8 units. It utilizes masterless automatic current-sharing technology, requiring no additional configuration.

Please select the corresponding model based on your input voltage, as well as your required output voltage and current. If you have any questions, please contact our sales engineers.

The standard operating temperature range is -10°C to +50°C. For outdoor applications, we recommend installing the unit inside a protective enclosure.

The typical efficiency is ≥85%, though specific figures may vary depending on the input and output voltage combination.

Scroll to Top